
Q. What is a constant
voltage power conditioner?
A. Although a constant voltage power
conditioner (sometimes referred to as constant voltage transformer or voltage regulator)
is a transformer like device, its design and function are totally different. The function
of a constant voltage power conditioner is to provide a voltage across its secondary
terminals within a specified tolerance (usually ±5%) as long as the voltage impressed on
the primary is within the specified bandwidth (usually +10% to -20%). See the
Power
Conditioning section for more information.
Back to Index
Q. What are the
differences between Sola power conditioners?
A. All three of these products use
Sola's patented ferroresonant technology. The primary design considerations for the
CVS
series were voltage stabilization and magnetic isolation. This group provides ±1% output
voltage regulation with an input voltage range of +10%/-20% with moderate (1000:1) normal
(transverse) noise attenuation.
The MCR series was designed
to address both voltage regulation and magnetic isolation. This group offers ±3% output
regulation with an input range of +10%/-20% but also offers magnetic isolation for
excellent 1,000,000:1 common mode and 1000:1 normal (transverse) mode attenuation.
The MPC series incorporates
all of the benefits of the MCR series in addition to exceeding the low leakage current
requirements of UL 544 and providing identifiable output receptacles to indicate they are
safe for hospital grade use (orange with green triangles).
The iSOLAtron is an
isolation transformer with special filtering to provide an extremely clean ground
reference. Although it contains some isolation from noise and surges, it does not regulate
the input voltage for swell and sag protection as in the CV, MCR and MPC series.
The Three Phase power
conditioners utilize microprocessor-based tap switching technology to provide ±5%
regulation in three phase installations. The CV, MCR and MPC are single phase only.
Back to Index
Q.
Can constant voltage power
conditioners be used to power motor loads?
A. Care needs to be exercised when
constant voltage power conditioners (CVPC) are used to power motor loads. When a motor is
energized, the lock rotor amperage required to get the motor started is normally 6 to 8
times the normal running amperage, or 600-800% of the load. When the load is increased
beyond the CVPC's rated value, a point is reached where the output voltage suddenly
collapses and will not regain its normal value until the load is partially released. Under
direct short circuit, the load current is limited to approximately 150-200% of the rated
full load value and the input watts to less than 10% of normal. Therefore, under short
circuit conditions, the Sola CVPC actually runs cooler than at no load.
A constant voltage power
conditioner, such as the MCR, will protect both itself and its load against damage from
excessive fault currents. Fusing of load currents may not be necessary. The actual value
of short-circuit current varies with the specific design and rating. Units may be operated
indefinitely at short-circuit. This characteristic protects the unit itself as well as the
load and load circuit being served. Typical overload performance is shown in the load
current chart below (Figure 1).
|

|
|
Figure 1
|
To properly size a constant
voltage power conditioner for use with a motor, be sure to size the CVPC so the nameplate
rating is equal to or greater than the lock rotor requirement of the motor.
Back to Index
Q.
Are there any special
considerations needed when I select a constant voltage power conditioner?
A. Special consideration must be given
to the type of load to be powered (inductive loads need to be sized to start up currents),
load power factor, ambient temperature and where the unit will be installed.
Back to Index
Q.
What exactly is
Ferroresonance?
A. Ferroresonance is the principle
behind Sola's very popular CVS, MCR and MPC power conditioners. Ferroresonance is the
property of a transformer design in which the transformer contains two separate magnetic
paths with limited coupling between them. The output contains a parallel resonant tank
circuit and draws power from the primary to replace power delivered to the load. Note that
"resonance" in ferroresonance is similar to that in linear circuits with series
or parallel inductors and capacitors, where the impedance peaks at a particular frequency.
In a nonlinear circuit, such as Sola's ferroresonant transformers, "resonance"
is used to reduce changes in supply voltage to provide a more consistent voltage to the
load.
A magnetic device is
nonlinear. Its reluctance changes abruptly above a certain magnetic flux density. At this
point, the magnetic device is defined as being in saturation. The design of the Sola
transformer allows one magnetic path (the resonant path) to be in saturation, while the
other is not (See Figure 2). As a result, further change in the primary voltage will not
translate into changes in the saturated or secondary voltage and voltage regulation
results.
|

|
|
Figure
2 |
Back to Index
Q.
How reliable is ferroresonant
technology?
A. The MTBF (mean time between failures
as measured in accordance with Mil. Std 217E) ranges from 10 to 25 years, depending on the
model, with typical life being approximately 50 years. All Sola Constant Voltage Power
Conditioners are backed by our exclusive 10 + 2 warranty.
Back to Index
Q.
Is there any problem with
phase shift between the input and output voltages of constant voltage power conditioners
(CVPC)?
A. The phase difference which exists
between input and output voltages is in the range of 120 degrees to 140 degrees at full
load. This phase differences varies with the magnitude and power factor of the load, and
to a lesser extent, with changes in line voltage and load power factor.
Back to Index
Q. We have experienced some temperature
problems with other makes of power conditioners. Has Sola addressed this problem?
A.
Sola's ferroresonant power
conditioners are very stable with respect to temperature. The change in output voltage is
only 0.025% per degree centigrade. Units are factory adjusted to +2%/-0% of nominal, with
full load and nominal input voltage. This adjustment to the high side of nominal is to
compensate for the natural temperature drift of about 1% that takes place during initial
turn on or warm up. When the unit warms up to operating temperature, the voltage typically
falls about 1%. This is why no load "cold steel" voltage measurements may be
slightly on the high side. At a stable operating temperature, the output voltage will
change slightly with varying ambient temperatures.
This shift is equal to
approximately 1% for each 40oC of temperature change. The normal maximum temperature rise
of a Sola power conditioner may fall anywhere in the range of 40oC to 110oC depending on
the type and rating. The nominal design ambient rage is between -20oC and +50oC. (-20oC
to +40oC for 70 to 1000 VA, 60 Hz portable models.)
Back to Index
Q.
Will harmonic currents affect
ferroresonant power conditioners?
A. A Sola ferroresonant power
conditioner will have essentially harmonic-free output because of the addition of a
neutralizing coil. This coil neutralizes the harmonics in a manner best explained by first
considering the device as a conventional transformer with the neutralizing coil
disconnected. Though this coil is now open circuited, it has a voltage induced in it as a
portion of the magnetic flux passes through the center leg of the core to the outer legs.
Since some of the primary flux links this coil, fundamental voltage is present. The
resultant voltage has a high odd-harmonic content due to the leakage flux from the output
winding.
This leakage flux can
return to the output winding by two paths. One bypasses the neutralizing coil. The other
path links the neutralizing coil completely. By controlling the reluctances of these
magnetic paths, one can control the degree of secondary flux coupled to the neutralizing
coil. The neutralizing coil is connected with its polarity additive to the secondary (or
output coil) as shown in Figure 3. The output of the newly formed regulator has constant
voltage with a waveshape almost completely free of harmonics.
|

|
|
Figure
3 |
The harmonics are still
present in the output winding and also in the neutralizing coil. Since those harmonics
present in the neutralizing coil are induced by the flux from the secondary winding, the
harmonics in each coil are approximately 180o out of phase. This results in their
cancellation. Proper control of turns ratio and magnetic path reluctance contribute to the
generation of a sinusoidal output - even with a square wave input!
Back to Index
Q.
Are there different constant
voltage power conditioner designs?
A. Yes, there are two basic design
concepts. A tap switching design utilizes an electronic circuit along with a traditional
transformer core and coil assembly to control the output voltage. As a result, the output
voltage tends to be a stepped waveform rather than a smooth sinewave.
A ferroresonant design
utilizes the electromagnetic induction principle exclusively to produce the desired output
voltage. Consequently, the output voltage waveform is a smooth sinewave. The ferroresonant
design attenuates transient electrical noise, provides surge suppression per ANSI/IEEE
Standards and provides a harmonic free output. These important benefits are not always
available with other designs.
Back to Index
Q.
Should I use a constant
voltage power conditioner instead of a UPS?
A. Your question involves two different
technologies used for differing reasons. 95% of all power quality problems are caused by
transient noise, voltage surges, harmonics or frequently changing voltage conditions.
Ferroresonant power conditioners provide the solutions for most all of these power quality
problems.
The primary function of any
uninterruptible power supply (UPS) is to provide an alternative voltage source (batteries)
to a critical load for some period of time should a complete a power failure occur.
Complete power failures account for less than 5% of all power quality problems. For the
other 95% of all power quality problems, unless the UPS is the on-line version, the UPS is
of no help.
Back to Index
Q.
How about response time? Will
constant voltage power conditioners work as well as other AC regulator types?
A. An important advantage of Sola's
ferroresonant CVPC is its exceedingly fast response time, compared with other types of AC
regulators. Transient changes in supply voltage are usually corrected within 1-1/2 cycles
or less; the output voltage will not fluctuate more than a few percent, even during this
interval.
Back to Index
Q.
Can single phase transformers
be banked together for three phase operation?
A. Yes, this is a common application.
Standard configurations include delta-wye and delta-delta connections. Advantages to
banking single phase units are:
- They are normally available
from local stocks.
- Offer greater application
flexibility.
- In the event of a failure of
one unit in a delta-delta connection, the other transformers can be made to operate in
open delta service at 57% of normal bank capacity.
While banking two or three
single phase transformers in a three phase bank is often expedient, it is more expensive
than using one three phase transformer.
Back to Index
Q.
What are voltage adjustment
taps?
A. In many instances, the supply
voltage delivered to the input (primary) of the transformer does not exactly match the
voltage rating described. If this happens, the output (secondary) voltage will vary from
its nameplate rating because the transformer turns ratio (voltage ratio) is fixed by
design. During design and manufacture of the transformer, additional terminations are
added to the primary winding to slightly alter the turns ratio. By closely matching the
voltage being applied to the appropriate tap, a desirable output voltage can be obtained.
Taps are typically located on the primary winding to correct for either sustained high or
low voltage conditions on the source. Taps are expressed as a percentage of the nameplate
voltage and are designated as FCAN (full capacity above normal) or FCBN (full capacity
below normal).
Back to Index
Q.
How and why is grounding of
transformers important?
A. Grounding removes static charges
that accumulate within a transformer. Grounding also reduces the chance of static
discharge causing personal harm and possible equipment damage should the transformer
windings accidentally come in contact with the core or enclosure. The actual method of
grounding a transformer is simple, defined in NEMA Publication No. ST20, Part 1, Page 4:
"ST20-1 19 GROUNDED
Grounded means connected to earth or to some extended conducting body which serves instead
of the earth, whether the connection is intentional or accidental. Effectively grounded
means grounded through a grounding connection of sufficiently low impedance that fault
grounds which may occur cannot build up voltages in excess of established limits..."
Before grounding, make sure
all contact surfaces are clean and free of any non-conductive protective coating. Any
surface where connections are made must be free of rust, scale and any impediments. Make
sure the flexible grounding jumper between the core and coil assembly and case is intact
and tight.
The metal enclosure, or
frame, of any transformer connected to a circuit operating at more than 30 Volts to ground
must be effectively grounded. A grounding conductor for the transformer will have a
current carrying capacity in accordance with either the National Electric Code or the
National Electrical Safety Code. Make sure grounding or bonding meets NEC and local codes.
For further information on grounding, refer to ANSI C1 and C2, NEC 1993 Article 250 and
NEMA ST20. These publications go into greater detail concerning grounding than space
permits here.
Back to Index
Q.
How does transformer
temperature relate to losses, BTU's and enclosures?
A. Transformers generate heat! They all
do. There is no way of getting around it. Heat is a by-product of the transformation
process and heat is due to losses in both the core and coils of the transformer. For most
applications, the heat generated is of little concern. But it becomes a concern when
determining how much cooling must be provided to compensate for the heat or when the
temperature of the enclosure could become a problem.
Transformer losses are
dependent on loading. A transformer operating at its nameplate KVA generates maximum
losses. This is considered to be 100% losses at 100% load, full load losses. A transformer
loaded at less than 100% doesn't generate as many losses, but it is not in direct
proportion to the amount of the load as indicated in the table below. Transformer losses
are expressed in watts.
| Description |
% Load
|
| 25% |
50% |
75% |
100% |
| % of total
heat losses generated (approx.) |
20% |
30% |
60% |
100% |
| % of
maximum top enclosure temperature (approx.) |
10% |
30% |
60% |
100% |
The top panel of a
transformer enclosure may reach a maximum surface temperature of 65°C (per NEMA ST20)
above the ambient temperature. In order to determine the total temperature of the
enclosure, add the ambient room temperature to the °C rise. Ambient temperatures may be
expressed in °F (Fahrenheit), so make sure to use the correct temperature conversion
scale:
°C
= .555(°F - 32)
°F = (1.8 x °C) + 32
Transformer losses are
measured in watts. Watts must be converted to British Thermal Units (BTU's) in order to
determine the amount of heat generated:
BTU's
= 3.41 x watts/hour
| Temperature Conversion Table |
| °C |
°F |
°C |
°F |
| 0 |
32 |
120 |
248 |
| 10 |
50 |
130 |
266 |
| 20 |
68 |
140 |
284 |
| 30 |
86 |
150 |
302 |
| 40 |
104 |
160 |
320 |
| 50* |
122* |
170 |
338 |
| 60 |
140 |
220 |
428 |
| 70 |
158 |
190 |
374 |
| 80 |
176 |
200 |
392 |
| 90 |
194 |
210 |
410 |
| 100 |
212 |
220 |
428 |
| 110 |
230 |
|
|
* Approximate threshold of
comfort for continuous touching.
Back to Index
Q.
How can transformer sound be
controlled?
A. All energized transformers
"hum". This "hum" is due to the alternating flux in the core producing
a phenomenon known as magnetostriction. Transformer "hum" , commonly referred to
as "noise", is primarily produced by the core at a fundamental frequency of
twice the applied frequency. Noise is an inherent characteristic of the core and cannot be
completely eliminated. Hevi-Duty utilizes the highest quality core steel in its complete
line of dry type transformers, to minimize audible sound levels.
When selecting a
transformer, make certain that the sound levels presented by the manufacturer have been
measured in accordance with the American National Standards Institute, and certified by
the manufacturer. NEMA Publication No. ST20 and ANSI Standard C89.2 establishes maximum
sound levels for dry type transformers. These levels are:
| KVA Range |
Maximum Sound Level |
| up to 9 KVA |
40 dB |
| 10 to 50
KVA |
45 dB |
| 51 to 150
KVA |
50 dB |
| 151 to 300
KVA |
55 dB |
| 301 to 500
KVA |
60 dB |
Hevi-Duty has low
transformer sound levels due to advanced designs and the manner in which the core and
coils are internally isolated from the enclosure. This is done by allowing the entire unit
to "float" on vibration dampening pads.
One of the major reasons
for transformer noise complaints is improper installation. Improper installation and
location can increase transformer sound levels 10 decibels or more. Considering that a 3
decibel increase in sound level has the effect of approximately doubling the sound volume
as detected by the human ear, a 10 decibel increase in sound level cannot (in most cases)
be tolerated.
The first step in low sound
level transformer installation is specifying the proper location. With the increased
popularity in cost saving advantages of high voltage distribution in modern buildings
today, it is necessary to locate small dry type transformers relatively close to (or
within) occupied areas. Transformers should be located in areas where the noise would be
the least objectionable. The maximum sound limit of the transformer to be installed should
be compared to the ambient sound level of the installation location. If the transformer is
expected to be louder than the ambient of the site, it should be located elsewhere.
Don't place a transformer
near multiple reflective surfaces. An example of a poor transformer location would be in a
corner near the ceiling or the floor. Either of these locations present three reflecting
surfaces, and these surfaces will act as a megaphone for the transformer sound. Halls are
undesirable too, because of the short distance between opposing reflecting surfaces.
When the best possible
location has been found, the next step is mounting. Transformers should be mounted on a
floor, wall or structure with as great a mass as possible. One guideline is that the
mounting surface should weigh at least ten times as much as the transformer. Take care not
to mount a transformer on a thin wall (i.e. plywood or a curtain wall) as they amplify the
noise much like a drumhead. The prime noise source in the transformer is in the core and
coil. The noise from this source is amplified and reflected by any structure solidly
connected to it. This includes incoming conduit and conductors. (Flexible devices may be
used for this purpose). Good transformer installations try to isolate the transformer from
all other components and structures.
Back to Index
Q.
Is one insulation system
better than another?
A. During recent years, the terminology
used by electrical equipment manufacturers regarding insulation systems has undergone a
major change. Letter designations, such as Class A, B, F and H are now Class 105, 150, 180
(sometimes referred to as 185) and 220 respectively. The preceding designations pertain
only to the rating of the insulation system. The transformer's rating has also been
changed - from Class A, B, F and H, to 55oC rise, 80° C rise, 115oC rise and 150oC
rise. What previously was a Class H transformer is now a 150oC rise transformer utilizing
a Class 220 insulation system.
The insulation rating is
the maximum allowable operating temperature for normal transformer life expectancy. The
insulation rating is the sum of the transformer rating, ambient operating temperature and
hot spot allowance. These maximum temperature limits are set by NEMA standards. Exceeding
any one of these will shorten transformer life expectancy.
A well designed
transformer, operating within the temperature limits of its insulation system, will have a
life expectancy of 20 to 25 years. The design life of transformers having different
insulation systems is the same, (lower temperature systems will have the same life as
higher temperature systems). The class of insulation used in a particular transformer is a
design consideration and such factors as voltage regulation, material cost and
availability are factors that the designer must consider.
Back to Index
Q.
What is balanced loading and
why is it important?
A. Balancing transformer loads means
being sure the transformer winding directly feeding a load is not overloaded beyond its
capacity. Most single phase transformer applications involve secondary windings rated for
120/240 Volts. These are frequently connected for three wire service. Since the
transformer has two 120 volt secondary windings, each one is capable of supplying only
one-half of the transformer's rated KVA capacity. If care is not taken, it is possible to
apply a combination of 120 and 240 volt loads that will, while not exceeding the total
nameplate rating, exceed the rating of one of the 120 Volt windings.
The same is true of three
phase transformers, especially those with 208Y/120 Volt or 480Y/277 Volt secondaries.
Remember, each of the three secondary windings of a three phase transformer has a maximum
capacity of one-third the nameplate KVA rating. It is always necessary to distribute the
single and three phase loads as evenly as possible across the three secondary windings
without exceeding their capacity.
Back to Index
Q.
What is impedance?
A. Impedance is defined as the vector
sum of resistance and reactance which limits the current flow in an AC circuit. When
dealing with a transformer, impedance indicates the current limiting effect should you
have a short circuit on the secondary. Expressed as a percentage and usually designated as
%IZ, impedance along with X/R ratio is used for coordination of fuses and/or circuit
breakers. It is also used for calculating the proper interrupting rating of overcurrent
protection devices.Calculate the interrupting capacity of a circuit breaker used to
protect the primary of a transformer using the following steps:
Example
If we had a 25 KVA, single phase, 60 Hz transformer, with a 480 volt primary, and 5%
impedance, we would first have to determine the full load primary amperage:
| Full Load
Primary Amps |
= |
(Nameplate
KVA rating x 1000) / Primary voltage |
|
= |
(25 x 1000) /
480 |
| 52.1 amps |
= |
25,000 / 480 |
Now determine maximum short
circuit current:
| Maximum
Short Circuit Current |
= |
Full load
primary amps / Impedance |
|
= |
52.1 amps /
5% |
| 1042 amps |
= |
52.1 / .05 |
The minimum interrupting
capacity the circuit breaker must have will be 1042 amps.
Typically impedance of
distribution transformers runs between 2% and 7%. These percentages vary depending on
manufacturer, transformer size, voltage, conductor material and many other factors.
Back to Index
Q.
What are the different NEMA
enclosure types and application definitions?
A.
| NEMA Enclosure Types |
| Type |
Description |
Typical Applications |
| NEMA-1 |
General
Purpose |
Indoor use;
Guard against incidental contact |
| NEMA-2 |
Drip-proof |
Indoor |
| NEMA-3 |
Protects
against wind blown dust, Rain-resistant |
Outdoor |
| NEMA-3R |
Rainproof |
Outdoor use
to protect against falling rain, sleet, and ice protection |
| NEMA-4 |
Water-tight,
Dust-tight |
Indoor or
outdoor use to protect against wind-blown dust and rain, splashing and hose directed water |
| NEMA-4X |
Water-tight,
Dust-tight, Corrosion-resistant |
Indoor or
outdoor use to protect against corrosion, wind-blown dust and rain, splashing and hose
directed water |
| NEMA-6 |
Submersible,
Water-tight, Dust-tight |
Indoor and
Outdoor |
| NEMA-7 |
Class I
(Hazardous) |
Indoor use
in Class I areas, per NEC |
| NEMA-8 |
Class I
(Hazardous) |
Indoor use
in Class I, oil-immersed equipment |
| NEMA-9 |
Class II
(Hazardous) |
Indoor use
in Class II areas, per NEC |
| NEMA-10 |
Bureau of
Mines |
|
| NEMA-11 |
Corrosion-resistant
& Drip-proof |
Indoor
oil-immersed |
| NEMA-12 |
Industrial
Use, Dust-tight |
Indoor use
to protect against dust, falling dirt and dripping noncorrosive liquids |
| NEMA-13 |
Oil-tight
and Dust-tight |
Indoor |
Back to Index
Q.
What are the UL enclosure
types?
A. Underwriters Laboratories adopted a
system for rating transformer enclosures which differs somewhat from the NEMA system. The
UL system lists just three enclosure types. A UL Type 1 enclosure is intended for indoor
service and offers a degree of protection from contact with the device inside the
enclosure. UL Type 2 enclosures are also intended for indoor service and provide
protection of the equipment inside the enclosure from limited amounts of falling dirt and
water. UL Type 3R enclosures can be used either indoors or outdoors and provide protection
against rain, sleet, snow and ice formation. The proper UL enclosure rating is listed on
the transformer nameplate.
Back to Index
Q.
Can 60 Hz transformers be used
on 50 Hz?
A. Yes. 60 Hz transformers can be used
on 50 Hz if special precautions are taken. The change in frequency will impact the flux
density of the transformer causing it to run hot, as if it were overloaded. To offset this
effect, you must decrease the input voltage by approximately 17% (1/6th). This means that
a transformer rated for a 480 Volt, 60 Hz input could run at 50 Hz but with a maximum
input voltage of 398 volts. On the other hand, 50 Hz transformers can be run on 60 Hz with
no ill effects.
Back to Index
Q. Is there a quick rule of thumb for
determining what transformer K-factor rating is needed for an
application?
A. Although it is not very scientific
and may result in a K-factor rating larger than actually needed, there is a quick and easy
method to ballpark K-factor. Take a look at all of the loads that will be powered by the
transformer. As you examine the loads ask yourself the following questions:
- What is the amperage draw of
this load while it is operating? Be sure to adjust inductive loads for their true power
consumption.
- Is the load electronic or
electrical? Many loads may be a hybrid of the two but try to put it into one
classification or another.
Once this has been done,
add up all of the "electrical" loads that will be on the circuit. Do the same
thing for "electronic" loads. When comparing the percentage of
"electrical" loads vs. "electronic" loads, if the transformer loading
is:
- 0% "electronic",
100% "electrical" - Use a standard (K-1 rated) transformer.
- 25% "electronic",
75% "electrical" - Use a K-4 rated transformer.
- 50% "electronic",
50% "electrical" - Use a K-9 rated transformer.
- 75% "electronic",
25% "electrical" - Use a K-13 rated transformer.
- 100% "electronic",
0% "electrical" - Use a K-20 rated transformer.
Although
"electronic" load will vary in their K-factor rating, by considering all
"electronic" loads to be the same, you are assured the sizing is correct and
most probably will allow for additional "electronic" loads to be added later.
Back to Index
Q.
What transformers should be
used for low voltage lighting applications and are there any special considerations?
A. Buck-boost transformers are ideally
suited for handing 12 or 24 Volt low voltage lighting. Although normally field connected
as an autotransformer and used for voltage correction, buck-boost transformers can also be
used as an isolation transformer to go from 120 or 240 Volts down to 12 and/or 24 Volts. A
few tips when using transformers for low voltage lighting applications:
- Be careful about the size of
the conductor running to the lights. Resistance in a wire decreases as you increase the
cross sectional size of the wire. In other words, the larger the gauge of wire, the lower
the resistance. The lower the resistance, the lower the voltage drop. Losing 2 Volts due
to line resistance can be critical when you're only starting with 12 Volts.
- Try to limit the length of
wire run. Again, the longer the run of wire, the greater the resistance. Many times you
are better off using two smaller sized transformers and have two lighting circuits.
- If possible, locate the
transformer in the middle of the lighting run. In other words, run parallel circuits
instead of one long continuous circuit. Be careful when using dimmers for low voltage
applications. Locate the dimmer on the low voltage side of the transformer. This will
result in a larger dimmer but dimming on the input (high voltage) side will impact the
operation of the transformer. We strongly recommend you to contact the dimmer manufacturer
for advice on your specific lighting application and to make sure that the dimmer is
designed and rated for use with magnetic loads.
Back to Index
Q.
How do I determine the correct
overcurrent protection for a 600 Volt class transformer?
A. A transformer has all the same
component parts as a motor, and like a motor, exhibits an inrush when energized. This
inrush current is dependent upon where in the sine wave the transformer was last turned
off in relation to the point of the sine wave you are when you energize the transformer.
Although transformer inrush could run up to 35 times full load current under no load, it
typically is the same as a motor...about 6 to 8 times normal running current. For this
reason it is important to use a dual element slow blow type fuse - the same type of fuse
you would use with a motor. If using a circuit breaker, select a breaker with a time delay
- again the same type you would use with a motor. If the time delay is not sufficient, you
may experience "nuisance tripping" - a condition where the breaker trips when
energizing the transformer but when you try it again, it works fine.
Secondary
overcurrent protection
Overcurrent devices are used between the output terminals of the transformer and the load for three reasons:
1. Protect the transformer from load electrical
anomalies.
2. Since short circuit current is minimized, a smaller gauge wire may be used between the
transformer
and the load.
3. Per NEC, a larger primary fuse may be used to reduce nuisance tripping.
Recommended
Fuse Sizes per UL508, NEC450.3(B) and NED430-72(C) are
below.
Back to Index
Q.
Are copper windings better
than aluminum windings?
A. As with most questions of this type
pertaining to transformers, a lot depends upon the application and the individual
preferences of the person specifying the transformer. Quite often the reason cited for
specifying copper windings is copper's high electrical conductivity.
During World War II, copper
became scarce and was used primarily for the war effort. Several industries turned to
aluminum as alternative to copper because it was in good supply, was very stable
price-wise and was less expensive than copper. In the 1940's, high-power transmission power
lines were converted from copper to aluminum and secondary power distribution networks
began utilizing aluminum in the 1950's. Today, virtually all standard transformer lines
from the major manufacturers are wound with aluminum. Although copper wound transformers
tend to be smaller than comparable aluminum wound transformers offer some distinct
advantages over copper wound units:
- Both copper and aluminum
oxidize over time. Aluminum conductors oxidize until all exposed aluminum surfaces are
covered with and oxide layer.At that point oxidation stops unless the aluminum oxide
barrier is somehow broken and the aluminum conductor is re-exposed to the air. Aluminum
oxide inhibits chemical reaction of the metal with the wire insulation. Aluminum oxide is
also a good electrical insulator. Copper on the other hand oxidizes completely over time.
Copper also acts as a mild catalyst, hastening the decay of the wire insulation. All of
these factors combine to give aluminum wound transformers a longer life than comparable
copper wound units, typically about five years.
- The heat storage capacity of
aluminum is approximately 2.33 times that of copper (specific heat of aluminum is 0.214
cal/gram/°C, specific heat of copper is 0.092 cal/gram/°C). With aluminum wound
transformers having a superior thermal storage capacity than copper wound units, they can
withstand more surge and overload currents than copper units (normal exhibited when a
motor starts.)
- Although the conductivity of
copper is better than that of aluminum, on a per pound basis aluminum is over twice as
good a conductor as copper.
Aluminum wire has received
a negative connotation over the year primarily because of the care that must be taken in
making connections. Copper proponents are quick to refer to hotel and mobile home fires
that occurred where aluminum wire was present. Upon close examination it was found that
the root causes of these problems is related to incorrect wiring devices being used.
Copper and aluminum expand at different rates when heated. If aluminum wire is used with
wiring devices solely rated for use with copper wire, the connection could loosen as the
connection heats up causing the resistance of the connection to increase and the
temperature to continue to escalate. Most transformer manufacturers address this problem
by making a transition between the aluminum windings, either to a copper lead wire (or bus
bar) or by terminating to an AI/Cu lug (or connector).
Q. So why are copper wound transformers
still specified?
A. Copper wound units may be specified
because of space limitations. Copper wound units can also be specified due to the
environment in which the transformer will be exposed. If the environment would be
corrosive to aluminum, copper wound transformers would make sense. Of course, some people
may just like copper wound transformers for their own reasons. Sola/Hevi-Duty manufactures
aluminum wound transformers but can manufacture copper wound transformers upon special
order. Contact your Sola/Hevi-Duty representative for pricing and manufacturing lead
times.
Back to Index
Q.
What is the capacity of the
center tap on a 240 delta connection with one phase tapped?
A. This is one of the most common
transformer application questions. If the transformer is a Sola/Hevi-Duty T5H series the
tap is full capacity, but we must define what full capacity means on one phase of a three
phase transformer. A three phase transformer built by Hevi-Duty in a ventilated enclosure
(standard construction on 15 KVA and above) has a per phase capacity equal to 1/3 of the
nameplate rating. Therefore, the tapped phase of a T5H30S has a total capacity of 10 KVA
(1/3 of 30 KVA). The 120 volt tap is at the center of this 240 volt winding so the
capacity is 5 KVA on either side of the tap (X1 to X6 and X3 to X6).
|
To determine the available
capacity of the center tap, you must know the three phase load applied to the 240 delta.
Each phase will supply 1/3 of the KVA to the three phase load. If the T5H30 has a 21
KVA,
3 phase load connected to it, each phase is loaded at 7 KVA. Therefore, the tapped phase
has 3 KVA available (10 KVA - 7 KVA = 3 KVA). The center tap can be loaded to 3 KVA
without over loading the transformer, but the load must be split so that no more than 1.5
KVA (1/2 the available capacity) is connected to either side of the tap (X1 to X6 and X3
to X6).
|

|
| Note: All
480 delta to 240 delta transformers stocked by Hevi-Duty are
equipped with a center tap. |
Back to Index
Q.
Ventilated transformers are
150°C rise, and Hard-shell® units are 115°C rise. Why are the Hardshell® units so
much warmer to the touch?
A. Ventilated transformers are free
standing devices placed in a metal housing to protect the unit from the atmosphere, and
people from electrical hazards. Ventilated units are surrounded by air, which acts as a
cooling medium. The natural convection created by the heat of the transformer causes heat
to ventilate through the top of the unit while cool air is drawn in from the bottom
(chimney effect).
Hardshell® are placed in
an enclosure that is filled with electrical grade sand and epoxy. All the air is displaced
within this solid epoxy block, so any heat is radiated directly to the enclosure surface.
This makes the entire enclosure of the transformer act like a heat sink. All
Sola/Hevi-Duty enclosed transformers are UL and CSA listed, your guarantee that the
surface temperatures will not rise more than 50°C above ambient.
Back to Index
Q.
What do the terms "peak
inrush current" and "exciting current" mean and how do they relate to
transformers?
A. Exciting current is the amount of
amperage a transformer draws under a no load condition. Another way to look at it is that
exciting current is the transformer's "idling" current. Exciting current could
also be referred to as no load current although this is not technically accurate. Exciting
current is actually made up of two components: no load losses (normally expressed in
watts) and reactive power (normally expresses in KVAR). Exciting current varies as a
percent of the transformer's nameplate rating depending upon the transformer size. It is
not unusual to have an exciting current of approximately 10% on very small transformers
(under 1 KVA). On larger transformers, exciting current could be as low as a half of one
percent.
Peak inrush current is the
amount of amperage a transformer draws instantaneously when it is turned on. A transformer
has an iron core and works under the principle of magnetic induction. Alternating current
flows through a coil of wire (primary winding) and generates a magnetic field. The iron
core of the transformer contains most of the magnetism and conducts this magnetism to
where it passes through a second coil of wire (secondary winding).
Since alternating current
travels in the form of a sine wave, the amount of magnetism will fluctuate depending upon
the point in the sine wave. As this magnetism cuts through the path of the second coil of
wire, it induces a voltage into it. When the transformer is turned off, the iron core
retains an amount of residual magnetism depending on where in the sine wave the unit was
when turned off. When the transformer is turned on, the greater the difference in the sine
wave from the "turn off" point to the "turn on" point determines the
amount of inrush current. Inrush current could be very small if everything was in phase,
or it could be as high as 20 to 30 times full load current. Although this inrush condition
disappears rapidly (in 6 to 10 electrical cycles - one tenth to one sixth of a second) it
is the first half electrical cycle that sees the peak amount of inrush. This condition can
cause problems with overcurrent devices. If the fuse or breaker is of a "quick
trip" variety or not properly sized according to the National Electric Code, the
inrush may cause it to trip falsely.
Back to Index
Q.
What is regulation?
A. Under no load, a transformer is not
providing voltage to the output. When a load is applied, the voltage will drop slightly.
The difference in the output voltage under load vs. unloaded is referred to as the
transformer's output regulation and is normally expressed as a percentage. If under no
load a transformer had an output voltage of 240 Volts but under load the output voltage
was 230 Volts, the difference would be 10 Volts and the regulation would be 10/240 or
4.17%. The power factor of the load can impact the transformer's regulation. General
purpose transformers can be used with a variety of loads, the most common being inductive
motor loads and resistive loads. For that reason, it is common to express transformer
regulation at 100% power factor and also at 80% power factor.
Back to Index
Q.
Can general purpose
transformers be used to power industrial control devices?
A. The answer to this question is
strictly application related. Industrial control transformers (sometimes referred to as
machine tool transformers or control transformers) are specifically design to meet the
demands required to power Industrial control devices such as contactors, solenoids and
relays. Industrial control devices typically have two power requirements - inrush capacity
(the power required to energize or seal the contacts) and sealed capacity (the power
required to keep the contacts sealed). It is not uncommon for inrush requirements to be 5,
10 or 15 times the sealed requirements.
It is critical that during
this period of time requiring the inrush VA requirement that the voltage powering the
device remain as steady as possible. Industrial control transformers are designed to
provide excellent voltage regulation under inrush conditions. Transformer design engineers
accomplish this via a number of different methods. Common methods include compensating
transformer secondary windings (to offset secondary winding losses), using a larger
conductor on the secondary windings (to cut winding losses) and designing a slightly
larger (and usually more expensive) transformer.
General purpose
transformers provide good voltage regulation up to full nameplate load but the output
voltage may drop slightly when the transformer is subjected to a momentary overload. This
voltage drop may be beyond what the industrial control device can tolerate. Care needs to
be taken if industrial control devices are to be powered from a general purpose
transformer. It is not recommended to use a general purpose unit if you are powering one
or two devices from the transformer or if you have multiple devices that all "turn
on" at the same time. A general purpose transformer may be preferable if you have
multiple devices to power that do not "turn on" at the same time and space
within the motor control panel is at a premium. Normally a general purpose transformer can
be located on the outside of the motor control panel.
Back to Index
Q.
Are there any special
considerations when powering electric motors?
A. Different product react differently
to motor loads and some are better suited for motor loads than others. For example:
- UPS products
(uninterruptible power supplies) are designed to provide power to critical loads where the
loss of power could cause massive problems (such as computer loads). Normally motor loads
are not considered to be critical. If your application rates a motor load as critical, you
must size the UPS to the inrush requirements of the motor (typically 6 to 10 times running
load current).
- Constant voltage power
conditioners are ferroresonant devices that provide clean, highly regulated power to
critical loads. Because of the design of the product, the output voltage of a constant
voltage power conditioner will go to zero when the load reaches 200% of nameplate rating.
Since motor inrush is typically 600 to 1000% of nameplate motor load, constant voltage
power conditioners must also be sized to the inrush demands of the motor. Unless
circumstances are highly unusual, neither UPS systems or constant voltage power
conditioners should be used with motor loads.
- Transformers are designed to
power motor loads. Although output voltage may momentarily drop when subjected to the
motor's inrush current, the transformer will act somewhat like a soft start device. If
your application calls for a motor to be powered from one transformer, the running load
amperage of the motor should not exceed 2/3 of the transformer's nameplate amperage rating
(66%). The reason is as voltage decreases due to motor inrush conditions, motor torque and
horsepower also drop proportionally. If voltage were to drop to 80%, torque and horsepower
would drop to 64% (80% squared). If torque were to drop to within 50% nameplate rating,
the motor could overheat due to excess current draw. This condition could exist without
tripping the overcurrent device and could result in failure of the motor or transformer.
Back to Index
Q.
What effect does ambient
temperature have on transformer operation?
A. Other conditions that need be
considered when sizing a transformer to a motor load are ambient temperature (derate the
transformer nameplate rating by 8% for ever 10°C above 40°C), altitude (derate
nameplate rating by 3% for every 300 feet above 3300 feet), and motor loads that
frequently start and stop. If a motor starts several times an hour (such as an air
conditioner), the calculated transformer size required should be increased by 20% to
offset the effects of inrush heating. If the motor starts very frequently (such as an
elevator), the service factor of the load must be used to calculate the proper transformer
size. If the service factor of the load is 1.25, the calculated transformer size should be
increased by 25%.
Remember:
Each 10oC over the rated temperature rise cuts the life of
your transformer by one half.
Back to Index
Q.
Can a Delta Primary (three
wire) transformer be used on a Wye (four wire) source?
A. Yes, any delta primary transformer
can be connected to a wye source simply by not using the neutral of the source. This
connection will not cause any adverse effects in the operation of the transformer or the
source.
Back to Index
Q.
Can transformers be operated
at voltages other than nameplate voltages?
A. In some cases transformers may be
operated at voltages less than nameplate voltage. In no case should a transformer be
operated at a voltage above nameplate voltage unless taps are provided for this purpose.
When operating below nameplate voltage the KVA rating of the transformer is reduced due to
the increase in current. For example a 10 KVA 480-240 transformer can have a secondary
load of 41.6 amps, if the same transformer was operated at 240-120 the same current draw
of 41.6 amps equates to a 5 KVA transformer.
Back to Index
Q.
Can transformers be reverse
connected?
A. All dry type transformers can be
reverse connected without a derating of KVA size, with certain limitations. All
Sola/Hevi-Duty three-phase transformers, and all single-phase transformers rated at 1 KVA
and above can be reverse connected without any loss in KVA rating. This is allowed due to
the turns ratio and the voltage ratio being equal.
Sola/Hevi-Duty does not
recommend reverse connecting single phase transformers less than 1 KVA since the turns
ratio compensation on the low voltage winding will provide voltages lower than name plate
voltage. This voltage will be lower for lower KVA sizes
Back to Index
Q.
Can a single-phase transformer
be connected to a three-phase source?
A. Yes, the transformer output will be
single phase. By connecting two wires from the source (three or four wire) to the
transformers primary leads. Care must be used to ensure transformer loading does not
create a phase imbalance on the source.
Back to Index
Q.
What is your
Warranty?
A. Sola/Hevi-Duty warrants its standard
catalog products to be free from defects in materials and workmanship and agrees to
correct by repair or replacement, at the option of Sola/Hevi-Duty, products that may fail
in service provided that the product has been installed, operated and maintained in
accordance with accepted industry practice.
Warranty begins upon date of manufacture and is according to the following schedule:
1. Standard catalog transformer and single phase, power
conditioning products 10 years plus an additional
2 years if the online
warranty
registration is completed within 14 days after installation.
2. Series TPC (Three Phase Power Conditioners) 2 years.
3. Uninterruptible Power Systems 2 years unless otherwise stated.
4. DC Power Supplies 1 year unless otherwise stated.
5. Products manufactured to a purchasers specifications 1 year.
Our obligation under the foregoing warranty, which is in lieu of all other expressed and
implied warranties including warranties of merchantability and fitness, is limited to
replacement or repairing of defective product provided we have received written notice of
any alleged defect within thirty (30) days after its discovery and, at our discretion,
return of products to the factory. Be sure to register your warranty
online.
Sola/Hevi-Duty shall not be liable for consequential, contingent, incidental or other
damages.
Back to Index
Q.
What is your UPC
Manufacturer's Identification Number?
A.
78-3472
Back to Index
Q. Where can I get a copy of the
MultiLink software for the
2000, 3000, 4000 and 5K UPS?
A. You can download it off of our
website. Click here.
Back to Index
Q. I am
getting 'Communications Loss - Not Protected'?
A. This
occurs when MultiLink software is not able to communicate with the monitored device.
 |
| |
Resolution:
The cable to the UPS is not connected securely or to the correct port on
the Computer or UPS.
You system is unable to open the serial port, possibly because of a port
conflict.
If connected to a MultiPort 8, you are not on the Smart Port.
If a MultiPort 4 is used, you must be connected to the built-in RS232
port on the UPS not the connector on the MultiPort 4.
The connected UPS is not a Series
3000, 4000
or S5kModular. We only
support these models for serial communications. If you do not have one of these models,
then you need to switch to contact closure method of communications. See Contact
Closure below.
An SNMP card is installed in the unit. When you install the SNMP
card in the Series 3000, 4000, S4k, or S5kModular the serial port on the DB9 connector
disables Transmit and Receive pins, but leaves the contact closure pins functioning. Your
only option is to use the contact closure method of communication. See Contact
Closure below.
You are using the cable that came in the box with the UPS, part number:
SML9P9S. This cable is wired for contact closure only. You can obtain the correct
cable (SML39P9S), or switch to the contact closure cable.
Contact Closure: If any one of the last three bullets above is true you
will need to change the Monitoring type to Contact Closure. Under the Overview tab, right
click on the device icon under MultiLink Device Network and select Properties. Change
the Device Type from Serial UPS to Contact Closure.
|

|
Back to Index
Q. How do I add licenses so I can shut
down more than one computer?
A. Go
to the drop down menu Configure and select Upgrade License.

|
| A window will
open and allow you to enter the location of the upgrade license. |
Back to Index
Q. How do I add the IP ad |