spacer
Sola/Hevi-Duty spacer
Home Search
What's New
Products
Cross Reference
Technical Support
Contact Us
Password Protected Area for Reps/Distributors
Product Specials

PDF Links
Printable version of Specifications and Selection Catalog Pages
Printable version of Specifications and Selection STV100K
Manual
Printable version of Specifications and Selection STV100K Dimensional Drawings


PDF files require Acrobat Reader
to view them.
Click above to download it
for free.

spacer Products
Home > Products > Surge & Noise Protection > STV 100K Surge Protection Device

STV100 K Hardwired Surge Series

STV100K.jpg (23059 bytes)

CUS

Sola/Hevi-Duty’s STV100K series Surge Protection Device (SPD's) is a hard wired SPD designed to be installed at the service entrance, branch panels or dedicated sensitive electronic loads. These surge protector feature all mode protection, LED and audible alarm status indication, sinewave tracking and Form C dry contacts. The STV100K series surge protector also contains the highest levels of safety built into the product including thermal fusing and a fault current fusing level of 65 kAIC.

These surge protector meet UL 1449, 2nd Edition standards and provide AIC ratings for appropriate and safe distribution panel use. These Surge Protection Devices come in a compact design allowing the user to install the product as close as possible to the sensitive load.

Surge protection is one part of a total power quality solution. Surge protector products can be used alone or in conjunction with other Sola/Hevi-Duty products to solve more complex power quality problems.

On this page: Related Products, Features, Dimensions, Specifications, Selection Table

Applications

  • Distribution Panels (<1200 A)
  • Branch, lighting and control panels
  • Factory automation installations
  • Dedicated industrial equipment

Printable versions of the following sections are available by selecting one of the pdf files to the left.

Related Products Top
 Features Top
  • 100,000 amp peak current rating to provide protection
    against severe transients
  • Low clamping levels for more effective protection
  • 65 kAIC fault current fusing level provides safety and NEC conformance
  • LED status and audible alarms
  • Listed to UL 1449, 2nd Edition, UL 1283.
  • Compact, rugged metal NEMA 12 enclosure
  • Thermal fusing prevents the MOV protection from overheating
    when exposed to high current levels.
Dimensions Top


100KDims.jpg (22049 bytes)

 

Specifications Top

 

Description

Catalog Number 

STV100K-10S STV100K-10N STV100K-24L STV100K-10Y

STV100K-23Y

 Input Voltage

120/240 V

120 V 240 V 208Y/120 V

380Y/220 V

Single Phase 3 wire + Ground

Single Phase 2 wire + Ground

Three Phase Wye 4 wire + Ground

 Maximum
 Continuous
 Operating
 Voltage (MCOV)

125% of the nominal level for 120 V; 115% for all other input voltages

 Line Frequency

47-63 Hz

 Connection
 /Mounting
 Type

Parallel/Flange

 Enclosure

Metal, NEMA 12 Enclosure

 Dimensions
 (H x W x D)

4 x 6 x 4 (inches)

 Weight

8 lbs. max

 Modes Of
 Protection

All Mode: L - N , L - L, L - G, N - G

 Safety Agency
 Approvals

UL 1449-2, cUL, UL 1283

UL 1449 (2nd Edition) Surge Protection Classification  

L-N 

400 V 400 V N/A 400 V

800 V

L-L 

800 V N/A 800 V 800 V

1500 V

L-G 

400 V 400 V 800 V 400 V 800 V

N-G 

400 V 400 V N/A 400 V 800 V
 AIC Rating

65 kAIC

 Status Indication

3-Green LEDs, 1 per phase, 1-Red LED, Form C Contacts, Audible Alarm

 Response Time

<0.5 nsec

 Operating
 Temperature

-40oC to +60oC

 Operating
 Humidity

0% to 95% Non-condensing

 Fusing

Thermal and Fault Current

 Noise
 Attenuation

40 dB Max

 Peak Surge Current Capability

Per Phase 

100 kA

100 kA

100 kA

100 kA

100 kA

Line to  Neutral 

50 kA

50 kA

N/A

50 kA

50 kA

Line to Line 

50 kA

N/A

50 kA

50 kA

50 kA

Line to  Ground 

50 kA

50 kA

50 kA

50 kA

50 kA

Neutral to  Ground 

50 kA

50 kA

N/A

50 kA

50 kA

 Warranty

10 Years

 

Selection Top

 

Description

Catalog Number
STV100K-27Y STV100K-24D STV100K-48D STV100K-10D4 STV100K-24D4

 Input Voltage

480Y/277 V

240 V

480 V

240/120 CT

480/240 CT

Three Phase Wye 4 wire + Ground

Three Phase D
3 wire + Ground

Three Phase D
4 wire + Ground

 Maximum
 Continuous
 Operating
 Voltage (MCOV)

125% of the nominal level for 120 V; 115% for all other input voltages

 Line Frequency

47-63 Hz

 Connection
 /Mounting Type

Parallel/Flange

 Enclosure

Metal, NEMA 12 Enclosure

 Dimensions
 (H x W x D)

4 x 6 x 4 (inches)

 Weight

8 lbs. max

 Modes Of
 Protection

All Mode: L - N , L - L, L - G, N - G

 Safety Agency
 Approvals

UL 1449-2, cUL, UL 1283

UL 1449 (2nd Edition) Protection Classification  

L-N 

800 V

N/A

N/A

400 V

800 V

L-L 

1500 V

1500 V

1500 V

800 V

1500 V

L-G 

800 V

1500 V

1500 V

400 V

800 V

N-G 

800 V

N/A

N/A

400 V

800 V

 AIC Rating

65 kAIC

 Status
 Indication
3-Green LEDs, 1 per phase, 1-Red LED, Form C Contacts, Audible Alarm
 Response Time

<0.5 nsec

 Operating
 Temperature

-40ooC to +60oC

 Operating
 Humidity

0% to 95% Non-condensing

 Fusing

Thermal and Fault Current

 Noise
 Attenuation

40 dB Max

 Peak Surge Current Capability

Per Phase 

100 kA

100 kA 100 kA

100 kA

100 kA

Line to  Neutral 

50 kA

N/A

N/A

50 kA

50 kA

Line to Line 

50 kA

50 kA

50 kA

50 kA

50 kA

Line to  Ground 

50 kA

50 kA

50 kA

50 kA

50 kA

Neutral to  Ground 

50 kA

N/A

N/A

50 kA

50 kA

 Warranty 10 Years

 


What's New | Products | Cross Reference | Technical Support | Contact Us | Search | Surge Protection Home

© 2000 Sola/Hevi-Duty. All Rights Reserved.

Sola/Hevi-Duty Hardwired Surge Protection