C US
|
Sola/Hevi-Dutys STV100K series Surge Protection Device (SPD's) is a hard wired SPD designed to be installed at the service entrance, branch panels or dedicated sensitive electronic loads. These surge protector feature all mode protection, LED and audible alarm status indication, sinewave tracking and Form C dry contacts. The STV100K series surge protector also contains the highest levels of safety built into the product including thermal fusing and a fault current fusing level of 65 kAIC.
These surge protector meet UL 1449, 2nd Edition standards and provide AIC ratings for appropriate and safe distribution panel use. These Surge Protection Devices come in a compact design allowing the user to install the product as close as possible to the sensitive load.
Surge protection is one part of a total power quality solution. Surge protector products can be used alone or in conjunction with other Sola/Hevi-Duty products to solve more complex power quality problems.
On this page: Related Products, Features, Dimensions, Specifications, Selection Table |
Applications
- Distribution Panels (<1200 A)
- Branch, lighting and control panels
- Factory automation installations
- Dedicated industrial equipment
|
Printable
versions of the following sections are available by selecting one
of the pdf files to the left.
- 100,000
amp peak current rating to provide protection
against severe transients
- Low
clamping levels for more effective protection
- 65
kAIC fault current fusing level provides safety and NEC conformance
- LED
status and audible alarms
- Listed
to UL 1449, 2nd
Edition, UL 1283.
- Compact,
rugged metal NEMA 12 enclosure
- Thermal
fusing prevents the MOV protection from overheating
when exposed
to high current levels.
Description |
Catalog Number |
| STV100K-10S |
STV100K-10N |
STV100K-24L |
STV100K-10Y |
STV100K-23Y |
Input
Voltage |
120/240 V |
120 V |
240 V |
208Y/120 V |
380Y/220 V |
Single Phase 3 wire + Ground |
Single Phase
2 wire + Ground |
Three Phase Wye 4 wire + Ground |
Maximum
Continuous
Operating
Voltage (MCOV) |
125% of the nominal level for 120 V;
115% for all other input voltages |
| Line
Frequency |
47-63 Hz |
Connection
/Mounting
Type |
Parallel/Flange |
| Enclosure |
Metal, NEMA 12 Enclosure |
Dimensions
(H x W x D) |
4 x 6 x 4 (inches) |
| Weight |
8 lbs. max |
Modes Of
Protection |
All Mode: L - N , L - L, L - G, N -
G |
Safety
Agency
Approvals |
UL 1449-2, cUL, UL 1283 |
UL 1449 (2nd Edition)
Surge Protection Classification |
L-N |
400 V |
400 V |
N/A |
400 V |
800 V |
L-L |
800 V |
N/A |
800 V |
800 V |
1500 V |
L-G |
400 V |
400 V |
800 V |
400 V |
800 V |
N-G |
400 V |
400 V |
N/A |
400 V |
800 V |
| AIC
Rating |
65 kAIC |
| Status
Indication |
3-Green LEDs, 1 per phase, 1-Red
LED, Form C Contacts, Audible Alarm |
| Response
Time |
<0.5 nsec |
Operating
Temperature |
-40oC
to +60oC
|
Operating
Humidity |
0% to 95% Non-condensing |
| Fusing |
Thermal and Fault Current |
Noise
Attenuation |
40 dB Max |
Peak Surge Current
Capability |
| Per Phase |
100 kA |
100 kA |
100 kA |
100 kA |
100 kA |
| Line to Neutral |
50 kA |
50 kA |
N/A |
50 kA |
50 kA |
| Line to Line |
50 kA |
N/A |
50 kA |
50 kA |
50 kA |
| Line to Ground |
50 kA |
50 kA |
50 kA |
50 kA |
50 kA |
| Neutral to Ground |
50 kA |
50 kA |
N/A |
50 kA |
50 kA |
| Warranty |
10 Years |
Description |
Catalog Number |
| STV100K-27Y |
STV100K-24D |
STV100K-48D |
STV100K-10D4 |
STV100K-24D4 |
Input
Voltage |
480Y/277 V |
240 V |
480 V |
240/120 CT |
480/240 CT |
|
Three Phase
Wye 4 wire + Ground |
Three Phase D
3 wire + Ground |
Three Phase D
4 wire + Ground |
Maximum
Continuous
Operating
Voltage (MCOV) |
125% of the nominal level for 120 V;
115% for all other input voltages |
| Line
Frequency |
47-63 Hz |
Connection
/Mounting Type |
Parallel/Flange |
| Enclosure |
Metal, NEMA 12 Enclosure |
Dimensions
(H x W x D) |
4 x 6 x 4 (inches) |
| Weight |
8 lbs. max |
Modes Of
Protection |
All Mode: L - N , L - L, L - G, N -
G |
Safety
Agency
Approvals |
UL 1449-2, cUL, UL 1283 |
UL 1449 (2nd Edition)
Protection Classification |
L-N |
800 V |
N/A |
N/A |
400 V |
800 V |
L-L |
1500 V |
1500 V |
1500 V |
800 V |
1500 V |
L-G |
800 V |
1500 V |
1500 V |
400 V |
800 V |
N-G |
800 V |
N/A |
N/A |
400 V |
800 V |
| AIC
Rating |
65 kAIC |
Status
Indication |
3-Green LEDs, 1 per phase, 1-Red
LED, Form C Contacts, Audible Alarm |
| Response
Time |
<0.5 nsec |
Operating
Temperature |
-40ooC to +60oC
|
Operating
Humidity |
0% to 95% Non-condensing |
| Fusing |
Thermal and Fault Current |
Noise
Attenuation |
40 dB Max |
Peak Surge Current
Capability |
| Per Phase |
100 kA |
100 kA |
100 kA |
100 kA |
100 kA |
| Line to Neutral |
50 kA |
N/A |
N/A |
50 kA |
50 kA |
| Line to Line |
50 kA |
50 kA |
50 kA |
50 kA |
50 kA |
| Line to Ground |
50 kA |
50 kA |
50 kA |
50 kA |
50 kA |
| Neutral to Ground |
50 kA |
N/A |
N/A |
50 kA |
50 kA |
| Warranty |
10 Years |