PDF files require Acrobat Reader
to view them.
Click above to download it
for free.
|
 |

SFL
Series, 75-600 Watt Power Supply
The
SFL series is a DIN Rail switching power supply series that complements
the Sola SDN products with more input voltage, output voltage and
power levels to give an even broader range of industrial DC power
solutions. These products are available in 12, 24 and 48 VDC output
and 115/230 VAC Input. They feature pluggable screw connectors (mating
connectors are included in each box sold) for easy installation
and service. The products feature a DIN Rail connection, front panel
DC OK indicators, easily accessible AC and DC connections.
For
parallel operation with power sharing, a redundant module option
is available for the 300 W (24 V/12 A) and 600 W (24 V/24 A) models.
On
this page: Features, Selection
Table, Specifications, Mounting
Brackets, Dimensions, Additional
Options
A
printable version of the following sections is available by selecting
the pdf file to the left.
| Features |
 |
- DIN
Rail Mount regulated switch mode power supplies
- 12
V, 24 V, and 48 V outputs available from 1.5-24 A
- Easy-to-wire
pluggable and screw terminal connectors
- Output
voltage adjustable
- Selectable
input: 115/230 VAC
- UL
508 Listed (except -RED versions). No derating necessary.
- UL1604
Listed for Class 1, Division 2 hazardous locations (except -RED
versions)
- Fully
Integrated Redundant and Remote Control Options:
- RED
(for SFL24-24-100 and SFL12-24-100 only):
Designed for N + 1 redundant power supply systems, these units
provide active current sharing and allow up to 5 power supplies
to be paralleled. Decoupling diodes and an alarm output to
signal a unit failure are included in this option. Multiple
units are required for redundancy.
- Models
with optional battery back-up available:
- UDS
(for SFL24-24-100 and SFL12-24-100 only)
Contact Technical Services for details.
Catalog
Number |
Input
Voltage Selectable |
Output
Power Maximum |
Output
Voltage Nominal |
Output
Current
Maximum
|
SFL6-12-100
SFL1.5-48-100 |
115/230
VAC |
75
Watt |
12
VDC
48 VDC |
6
A
1.5 A |
| SFL3-48-100 |
115/230
VAC |
150
Watt |
48
VDC |
3
A |
SFL12-24-100
SFL6-48-100 |
115/230
VAC |
300
Watt |
24
VDC
48 VDC |
12
A
6 A |
SFL24-24-100
SFL12-48-100 |
115/230
VAC |
600
Watt |
24
VDC
48 VDC |
24
A
12 A |
| Redundant
Models |
SFL12-24-100RED
SFL24-24-100RED |
115/230
VAC |
300
Watt
600 Watt |
24
VDC |
12
A
24 A |
|
Parameter
|
Value
|
|
Input
|
| Input
Voltage Nominal (user selectable) |
93-132
VAC / 187-264 VAC
|
| Fin:
Input Frequency |
47-63
Hz
|
| Input
current at full load (typical)
|
115
VAC |
230
VAC |
| -75
W (12 V/6 A, 48 V/1.5 A) |
1.7
A |
0.9
A |
| -150
W (24 V/6 A, 48 V/3 A) |
3.0
A |
1.7
A |
| -300
W (24 V/12 A, 48 V/6 A) |
5.4
A |
3.3
A |
| -600
W (24 V/24 A, 48 V/12 A) |
10.5
A |
6.4
A |
| Input
current (max.) |
115
VAC |
230
VAC |
| -75
W |
16.5
A |
33.0
A |
| -150
W |
35.0
A |
70.0
A |
| -300
W |
35.0
A |
70.0
A |
| -600
W |
70.0
A |
80.0
A |
| Internal
Fuse (slow burn) |
| -75
W/150 W |
4.0
A |
| -300
W |
6.3
A |
| -600
W |
12.0
A |
|
Output
|
| Voltage
Adjustment Range |
| -12
V models |
12
- 14 VDC
|
| -24
V models |
24
- 28 VDC |
| -48
V models |
48
- 52 VDC |
| Output
Regulation |
| -
Line voltage variation |
±0.2%
max.
|
-
Load variation 1090%
75W, 150W Models
300W,
600 W Models |
±1.0% max
±0.5%
max.
|
| Ripple
and noise (20 MHz bandwidth) |
<50
mVpp |
Electronic
short circuit protection/
current limitation |
110%
typ. (constant current) |
Parallel
Operation
-SFL12-24-100RED & SFL24-24-100RED |
Up to 5 units |
| IMAX:
Overvoltage Protection, trigger point at |
140%
typical out nominal |
| th:
Holdup Time |
min.
20 ms |
|
General
|
TA:
Operating Temperature Range
Derating above 50°C |
-25°C...+70°C
2%/°C
|
| TS:
Storage Temperature |
25°C...+85°C
|
| Humidity
(non condensing) |
95%
rel H max.
|
Switching
Frequency
- 75 W
- 150 W/300 W/600 W |
100 kHz typical
67 kHz typical
|
| Efficiency |
>85% |
| Operation
Indication |
LED,
DC OK |
Isolation
Voltage
- Input/output
- Input/case
- Output/case |
3,000 VAC (1 minute)
2,000 VAC (1 minute)
500 VAC (1 minute)
|
| Safety
Class (IEC536) |
Class
1
|
| Safety
Standards Met |
IEC950,
EN60950, CE marked for LVD,
UL1950 recognized and UL 508
|
| Conducted
EMI according to: |
EN55022
Class B, EN55011 Class B, FCC-B
|
Electromagnetic Suspectibility
-Electrostatic discharge ESD
-RF field suspectibility
-Electrical fast transients/ bursts on mainsline
-Immunity to conducted radio frequency
disturbances above 9 kHz.
- Mains frequency field |
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-6
EN61000-4-8
|
4 kV/8 kV
10 V/m
2 kV
10 V
30 A/m
|
| Case
protection according to IEC529 |
IP20 |
| Case
Material |
Steel |
| Mounting |
Snap-on
35 mm DIN Rail as per EN50022 or
Chassis mounting option available.
|
Catalog
Number |
Output
Power
Maximum |
| SFL75-PMBRK |
75
Watt |
| SFL150-PMBRK |
150
Watt |
| SFL300-PMBRK |
300
Watt |
| SFL600-PMBRK |
600
Watt |
|

|
|
SFL
75 Watt (12V/6A, 48V/1.5A)
|
|

|
|
SFL 150 Watt (SFL3-48-100)
|
|

|
|
SFL
300 Watt (SFL12-24-100RED, SFL6-48-100)
|
|

|
|
SFL
600 Watt (SFL12-48-100, SFL24-24-100RED)
|
What's New |
Products |
Cross Reference |
Technical Support |
Contact Us |
Search |
Power Supply Home
© 2000
Sola/Hevi-Duty. All Rights Reserved.
Sola/Hevi-Duty Power Supplies - Power Supply / Din Rail Products
|
 |