SDN Series Power Supply (Single and Three Phase Units, 60-960 Watts)
The SDN DIN Rail power supply products provide industry leading performance. Sag immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications. Power factor correction to meet European directive, hazardous location approvals and optional redundant accessories allow the SDN series to be used in a wide variety of applications. Wide operation temperature range, high tolerance to shock and vibration and reliable design make the SDN series the definition of DC power quality.

Quick Overview:

A printable version of the following sections is available by selecting the pdf file to the left.

Features Top
 
  • Power Factor Correction (per EN61000-3-2)
  • Auto Select 115/230 VAC, 50/60 Hz Input
  • Single Phase models meet SEMI F47 Sag Immunity
  • Class 1, Div 2 Hazardous Locations
  • Improved metal mounting clip
  • DC OK Signal 
  • Adjustable Voltage
  • SDN10-24-100P New Compact width (3.26”)
  • Industrial grade design
      - 10oC to 60oC operation without derating. Indefinite short circuit, 
         overvoltage and overtemperature protection. 
      - Powers high inrush loads without shutdown or foldback
      - Rugged metal case and DIN connector
  •  
  • Parallel Capability standard on all units
  • Broad range ( 2.5 A through 40 A) of product to fit almost any application
  • Narrow width on rail for space critical applications
  • SDN2.5-24-100P and SDN4-24-100LP meet NEC Class 2
  • User-friendly front panel. 
    - Large, rugged, accessible, multiple connection screw terminations 
    - Easy installation

SDN-P DIN Rail Power Supply Features

  • High MTBF and reliability
  • Five year warranty
  • Single and three phase inputs available
  • Highly efficient >90% switching technology
  • Patented


EMC and 
Low Volt.
Directive


UL 508 Listed 
IND CONT. EQ. 
E61379


UL 60950
E137632
cUL/CSA-C22.2
No. 234-M90
Related Products Top
Applications Top

  • Industrial/Machine control
  • Vending Machines
  • Process control
  • Packaging Equipment
  • Material Handling
  • Amusement Park Equipment
  • Conveying Equipment
  • Semiconductor Fabrication Equipment
  • DeviceNetTM
 
Accessories Top

  • Chassis Mount Bracket (SDN-PMBRK2)  

Specifications (Single Phase) Top

Description

Catalog Number

SDN 2.5-24-100P

SDN 4-24-100LP SDN 5-24-100P SDN 10-24-100P SDN 20-24-100P

Input

 Nominal
 Voltage

115/230 VAC user select (no manual required)

   -AC Range

85-132/176-264 VAC

   -DC Range 

90-375 VDC

210 - 375 VDC

N/A

   -Frequency

47 - 63 Hz

 Nominal Current1

1.3 A / 0.7 A

1.8 A / 0.9 A 2.2 A / 1.0 A 5 A / 2 A typical 9 A / 3.9 A
   -Inrush
    current max.
    typ. <25 A
typ. <20 A typ. <40 A
 Efficiency
  (Losses2)

>87.5% typ 
(8.6 W)

>88% typ 
(13.1 W)
>88% typ (16.4 W) >88% typ
(32.7 W)
>90% typ 
(48 W)
 Power Factor
 Correction
Units fulfill EN61000-3-2

Output

 Nominal Voltage

24 VDC (22.5 - 28.5 VDC Adj.)

   -Tolerance

<±2% overall (combination line, load, time and temperature related changes)

   -Ripple3 

< 50 mVpp

 Nominal Current

2.5 A (60 W)

3.8 A (92 W)

5 A (120 W)

10 A (240 W)

20 A (480 W)

  -Peak Power4

1.6x Nominal Current
< 2 sec.

4.2 A max at 23.8V  

6 A
2x Nominal Current
< 2 sec.

12 A
2x Nominal Current
< 2 sec.

25 A
2x Nominal Current
< 2 sec.

 -Current Limit  Fold Forward (Current rises, voltage drops to maintain constant power during overload up to max peak current)
 Holdup Time

> 50 ms

> 110 ms
> 100 ms
> 20 ms
 Parallel Operation
 Single or Parallel use is selectable via Front Panel

General

 EMI
   -Emissions
 EN50081-1,-2 Class B EN55011, EN55022 Radiated and Conducted including Annex A.
   -Immunity  EN50082-1, -2; EN61000-4-2 Level 4, EN61000-4-3 Level 3; EN61000-4-6 Level 3; EN61000-4-4 Level 4
 input and Level 3 output; EN61000-4-5 Isolation Class 4, EN61000-4-11; Transient resistance according to VDE 0160/W2 over entire
 load range.
 Approvals  EN60950; EN50178; EN60204; UL508 Listed, cULus; UL60950, cRUus, CE (LVD 73/23 & 93/68/EEC). EN61000-3-2, IEC60079-15 (Class 1, Zone 2, Hazardous Location, Groups A, B, C, D, w/T3A temp class up to 60oC Ambient) SEMI F47 Sag Immunity. SDN2.5 & SDN4 -UL60950 testing to include approval as NEC Class 2 power supply acc. to NFPA 70 art. 725-41 (a)(2).
 Temperature Storage: -25oC...+85oC Operation. -10o-60oC full power with operation to 70oC possible with a linear derating to half power from 60oC to 70oC (Convection cooling, no forced air required). Operation up to 50% load permissable with sideays or front side up mounting orientation. The relative humidity is 95% RH, noncondensing; IEC68-2-2, 68-2-3. For operation below -10oC, contact Technical Services.
 Warranty

5 years

 General
 Protections/
 Safety
 Protected against short-circuit, overload, open-circuit. Overvoltage protection (OVP) for output set  >30.5 but <33 VDC, Auto Recovery.
 Protection class I (IEC536), degree of protection: IP20 (IEC 529) Safe low voltage: SELV (acc. EN60950).
 Status
 Indicators
 Green LED and DC OK signal (N.O. Contacted rated 300 mA @ 60 VDC)

Installation

 Fusing
   -Input

 Internally fused. External 10 A slow acting fusing for the input is recommended for SDN2.5, 4 5 and 10P models. A 16A slow acting fuse or time-delay circuit breaker is recommended for the SDN20 model.

   -Output

Outputs are capable of providing high currents for short periods of time for inductive load startup or switching. Fusing may be required for wire/loads if 2x Nominal O/P current rating cannot be tolerated. Continuous current overload allows for reliable fuse tripping.

 Mounting

 Simple snap-on system for DIN Rail TS35/7.5 or TS35/15 or chassis-mounted (optional screw mounting set SDN-PMBRK2 required).

 Connections  Input: IP20-rated screw terminals, connector size range: 16-10 AWG (1.5-6 mm2) for solid conductors. 16-12 AWG (0.5-4 mm2) for stranded conductors. 
 Output: Two connectors per output, connector size range: 16-10 AWG (1.5-6 mm2) for solid conductors.
 Case

 Fully enclosed metal housing with fine ventilation grid to keep out small parts

   -Free Space

25 mm above/below
25 mm left/right
10 mm in front

25 mm above/below
25 mm left/right
15 mm in front

70 mm above/below
25 mm left/right
15 mm in front

 H x W x D
 (inches/mm)

4.88 x 1.97 x 4.55
(124 x 50 x 116)
 

4.88 x 2.56 x 4.55
(124 x 65 x 116)
 

4.88 x 3.26 x 4.55
(124 x 83 x 116)

4.88 x 6.88 x 4.55
(124 x 175 x 116)

 Weight (lbs/g)

1.6 lb (725g) 

2.4 lb (1055g) 

3.3 lbs (1480g) 3 lbs (1520g)
Notes:
1. Input current ratings are conservatively specified with low input, line conditions, worst case efficiency and power factor.
2. Losses are heat dissipation in watts at full load, nominal input line.
3. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor.
4. All peak power is calculated at 24 Volt levels.
5. Full load, 100VAC Input @ Tamb = +25oC

 

Specifications (Three Phase) Top

Description

Catalog Number

SDN 5-24-480

SDN 10-24-480

SDN 20-24-480C SDN 30-24-480 SDN 40-24-480

Input

 Nominal  Voltage

1Æ or 3Æ, 380 - 480 VAC

1Æ or 3Æ, 380 - 480 VAC1 3Æ 380-480 VAC
   -AC Range

340-576 VAC

   -DC Range  450 - 820 VDC
   -Frequency

47 - 63 Hz

 Nominal Current2 0.5 A 0.8 A 1.5 A 2.0 A 3.0 A
   -Inrush current typ. < 18 A typ. < 30 A
 Efficiency
 (Losses2)
>90% typ (12 W) >90% typ (48 W) >90% typ (72 W) >90% typ (96 W)
 Power Factor
 Correction
Units fulfill EN61000-3-2

Output

 Nominal Voltage

24 VDC (22.5 - 28.5 VDC adj.)

   -Tolerance

<±2% overall (combination line. load, time and temperature related changes)

   -Ripple4  < 50 mVpp
 Nominal Current

5 A (120 W)

10 A (240 W)

20 A (480 W)

30 A (720 W)

40 A (960 W)
   -Peak Current

6 A 
2x Nominal Current 
< 2 sec.

12 A 
2x Nominal Current 
< 2 sec.

25 A 
2x Nominal Current 
< 2 sec.

35 A 
2x Nominal Current 
< 2 sec.

45 A 
2x Nominal Current 
< 2 sec.

   -Current
     Limit 

Fold Forward 
(Current rises, voltage drops to maintain constant power during overload up to max peak current)

 Holdup Time

>40 ms

>28 ms

>20 ms
 Parallel
 Operation
5A through 30A units may be passively paralleled  by selecting the "P" position of the switch on the unit.  The SDN40 contains active current balancing.

General 

 EMI
   -Emissions

   -Immunity
EN61000-6-3, -4; Class B EN55011, EN55022 Radiated and Conducted including Annex A.
EN61000-6-1, -2; EN61000-4-2 Level 4, EN61000-4-3 Level 3; EN61000-4-6 Level 3; EN61000-4-4 Level 4 input and Level 3 output; EN61000-4-5 Isolation Class 4, EN61000-4-11; Transient resistance according to VDE 0160/W2 over entire load range.
 Approvals CB Scheme, EN60950; EN50178; EN60204; UL508 Listed, cULus; UL60950, cRUus, CE (LVD 73/23 & 93/68/EEC). EN61000-3-2, IEC 60079-15 (Class 1, Zone 2 hazardous location, Groups IIA, IIB, IIC w/T3 temp class up to 60°C Ambient.) 
 Temperature Storage: -25oC...+85oC Operation. -10o-60oC full power with operation to 70oC possible with a linear derating to half power from 60oC to 0oC. (Convection cooling, no forced air required). Operation up to 50% load permissable with sideways or front side up mounting orientation. The relative humidity is less <90% RH, noncondensing; IEC 68-2-2, 68-2-3.
 Warranty

5 years

 General 
 Protection/
 Safety
Protected against continuous short-circuit, overload, open-circuit. Protection class 1 (IEC536), degree of protection IP20 (IEC 529) Safe low voltage: SELV (acc.EN60950)
 Status Indicators  Green LED on, when Vout = 18V or greater. 

Installation

 Fusing
   -Input  Internally fused.
   -Output Outputs are capable of providing high currents for short periods of time for inductive load startup or switching. Fusing may be required for wire/loads if 2x Nominal O/P current rating cannot be tolerated. Continuous current overload allows for reliable fuse tripping.
 Mounting Simple snap-on system for DIN Rail TS35/7.5 or TS35/15 or chassis-mounted (optional screw mounting set SDN-PMBRK2 required).
 Connections  Input: IP20 related screw terminals, connector size range: 16-10 AWG (1.5-6 mm2) for solid conductors. 
            16-12 AWG (0.5-4 mm2) for stranded conductors. 
 Output: two connectors per output, connector size range: 16-10 AWG (1.5 - 6 mm2) for solid connectors.
 Case

 Fully enclosed metal housing with fine ventilation grid to keep out small parts.

   -Free Space

25 mm above/below
25 mm left/right
15 mm in front

70 mm above/below
25 mm left/right
15 mm in front

 H x W x D
 (inches/mm)

4.88 x 2.91 x 4.55
(124 x 73 x 116)

4.88 x 3.5 x 4.55
(124 x 89 x 116)

4.88 x 5.9 x 4.55
(124 x 150 x 116)

4.88 x 9.72 x 4.55
(125 x 247 x 116)

4.88 x 11.1 x 4.55
(125 x 282 x 116)

 Weight (lbs/g)

1.7 lbs (730g)

2.16 lbs (980g)

3.97 lbs (1800g)

4 lbs (2000g) 6.6 lbs (3300g)
 Notes:
 1.  For the SDN20-24-480C, single phase input is permissible but output is derated to 75% (15 Amps @ 24 VDC). 
 2.  Input current ratings are conservatively specified with low input, worst case efficiency values and power factor. 
 3.  Losses are heat dissipation in watts at full load, nominal input line.
 4.  Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor.

 

Dimensions Top

 

Catalog 
Number
Dimensions
H W D
 SDN 2.5-24-100P

4.88 (124)

1.97 (50)

4.55 (116)

 SDN 4-24-100LP 4.88 (124)

2.56 (65)

4.55 (116)
 SDN 5-24-100P 4.88 (124) 2.56 (65) 4.55 (116)
 SDN 5-24-480 4.88 (124)

2.91 (73)

4.55 (116)
 SDN 10-24-100P 4.88 (124) 3.26 (83) 4.55 (116)

 



Catalog
Number
Dimensions
H W D
 SDN 20-24-100P 4.88 (124) 6.88 (175) 4.55 (116)
 SDN 10-24-480 4.88 (124) 3.50 (89) 4.55 (116)
 SDN 20-24-480C 4.88 (124) 5.90 (150) 4.55 (116)
 SDN 30-24-480 4.88 (124)

9.72 (247)

4.55 (116)
 SDN 40-24-480 4.88 (124) 11.10 (282) 4.55 (116)

 

SDN Series Mounting Top

DIN Rail Mounting

Snap on the DIN Rail:

1. Tilt unit slightly backwards.

2. Put it onto the DIN Rail.

3. Push downwards until stopped.

4. Push at the lower front edge to lock.

5. Shake the unit slightly to ensure
    that the retainer has locked.

SDNMount.JPG (24768 bytes)


Alternative Screwing-on:

  • Using the optional SDN-PMBRK2 accessory, the unit can also be screwed onto plane surfaces 
    (without DIN Rail).
Detachment from DIN Rail:

 Press button downwards (to unlock) and remove the
 unit from the DIN Rail.

 

Chassis Mounting Top

Instead of snapping a Sola SDN power supply unit on the DIN Rail, you can also attached it using the screw mounting set SDN-PMBRK2.
This set consists of two metal brackets which replace the existing two aluminum profiles.

Note:

You need one SDN-PMBRK2 per unit.
In addition, two screws are required per SDN-PMBRK2 (e.g. M5 x 12), which are not included with the set.

Dimensions Top

 

 

Exchanging the Profiles Top
At the unit:
  • Remove the screw from the profile.
  • Pull the profile outwards to remove.

  • Push the SDN-PMBRK2 profile into the
    groove as far as possible.
    Secure with screw.

Note the orientation: The profile fits into the groove only as shown here.

For SDN5-24-100P 
and above models.

For SDN2.5-24-100P model



What's New | Products | Cross Reference | Technical Support | Contact Us | Search | Power Supply Home

© 2000 Sola/Hevi-Duty. All Rights Reserved.

Sola/Hevi-Duty Power Supplies - Power Supply / Din Rail Products