Input |
|
Nominal Voltage |
Any voltage from 100 to 240 Vac Input |
|
-AC Range |
85-264 Vac Universal Input |
|
-DC Range |
100-353 Vdc |
|
Nominal Current1 |
1.6A/0.7A |
|
-Inrush current max. |
Typ. <25A |
|
Power Factor Correction |
0.95 |
|
Frequency |
50/60/400 Hz |
|
Output |
|
Power Back Immunity |
35V |
|
Overvoltage Protection |
25-25.5 Vdc, autorecovery |
|
Nominal Voltage |
24 Vdc |
|
Tolerance |
< +/-2% overall (combination line, load, time and temperature
related changes). |
|
- Line Regulation |
< 0.5% |
|
- Load Regulation |
< 0.5% |
|
- Time & Temp. Drift |
< 1% |
|
Ripple2 |
< 50mVpp |
|
Nominal Current |
3.8A |
|
Holdup Time |
> 25ms (Full load, 100Vac Input @ Tamb=+25o) to 95% output
voltage |
|
General |
|
Case |
IP66/67 versatile ingress protection; also meets UL50 Type 4X
enclosure. |
|
Min. Required Free Space |
1 in. (25 mm) all sides but mounted base (permissible to mount
in any orientation) |
|
H x W x D (inches/mm) |
4.7 in. x 7 in. x 1.8 in.(119 mm x 178 mm x 46 mm) |
|
Weight (lbs/kg) |
2.6 lbs (1.16 kg) |
|
EMC |
|
|
Emissions |
EN61000-6-3, EN61204-3, EN55022 Class B, EN61000-3-2,
EN61000-3-3 |
|
Immunity |
EN61000-6-2, EN61204-3, EN55024, IEC61000-4-2, IEC61000-4-3,
IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8,
IEC61000-4-11 |
|
Approvals |
UL508, cULus; UL60950, cULus; UL60079-15 cRUus; IEC60950; CE (LVD
73/23 & 93/68/EEC).
(EMC 89/336 & 93/68/EEC). EN61000-3-2,
EN50021 (Class 1, Division 2 Hazardous Location, EEX nA IIC T4 U up to 60°C Ambient.)3 UL2043
|
|
|
Storage: -40o to +85oC, Operation: -40o to +60oC full power with
linear derating to half power from 60o to 70oC (Convection
cooling, no forced air required). Operation up to 100% load
permissible with sideways or front side up mounting
orientation. |
|
Humidity |
Up to 100% RH with condensation. |
|
Altitude |
0 to 3,000 meters (0 to 10,000 feet) |
|
Vibration |
1.0 gravity (g) peak, 10-500 Hz (random wave). Passed random vibration test conditions for 3 axes for 60 minutes duration while energized and operating. |
|
Shock |
4 g peak, 22 milliseconds half-sine pulse, 3 times on 6 faces while energized and operating |
|
Warranty |
5 years |
|
MTBF |
>500,000 hours according to Telcoredia/Bellcore SR-332 Issue 1,
(Vin 120Vac, Tamb=40oC) |
|
General Protection/Safety |
Protected against continuous short-circuit, continuous overload,
continuous open circuit. Protection class 1 (IEC536), degree of
protection IP66/67 versatile (IEC 529). Safe low voltage: SELV
(acc. IEC60950) |
|
Status Indicators - Visual |
DC OK LED |
|
Installation |
|
Fusing |
|
|
-Input |
Internally fused, fuses not replaceable |
|
-Output |
Inherently limited current to meet Class 2 requirements per
UL1310 |
|
Mounting |
Chassis mounted via built in mounting tabs. Removal and
replacement of the unit shall be possible from front of panel. |
|
Connections |
Input: 3 pin IP67 molded plug (quick disconnect). Output: 4 pin
IP67 molded receptacle (quick disconnect). |
1.
Input current ratings are specified with low input, line
conditions, worst case efficiency values and power factor.
2. Ripple/noise is stated as typical
AC values when measured with a 20 MHZ, bandwidth scope and 50
Ohm termination.
3.
Additional installation requirements apply
when used in hazardous locations (refer to user manual).
|