PDF files require Acrobat Reader
to view them.
Click above to download it
for free
|
 |

SOLATRON
Plus Series - Three Phase Power Conditioner
|
These three phase power conditioner units protect equipment from voltage sags and spikes, switching transients, lightning, and induced surges by a carefully designed surge suppression circuit linked to a shielded isolation transformer and input and output filters.
These power conditioner units hold output voltage regulation to a maximum of ±5%, even with an input voltage window of +15% to -25%. Response time to any line variation is
1.5 cycles regardless of power factor. The power conditioner units operate with 150 dB Common Mode noise attenuation and 65 dB Normal Mode noise attenuation at 100 kHz.
|
|
| On
this page: Features, Applications,
Related Products, Specifications,
Selection Table |
c US
|
A printable version of the following sections is available by selecting the
pdf file to the left.
- Rugged, industrial design
- High overload capability
- High MTBF - No fans used
- No power factor restriction on loads
- Tight regulation of ±3% for protection against sag (-25%) and swell (+15%) conditions
- Failsafe, no-break, auto-bypass
- Status indicating lights
- Shielded, copper wound isolation transformer
- Surge suppression to ANSI/IEEE and IEC Standards
- High efficiency (96%) microprocessor controlled tap switcher
- Automatic under voltage protection
- UL1012, UL1449-2, cULus Listed
|
- Automatic Packaging Machinery
- Data Rooms
- UPS Bypass Circuits
- Retail Store
- Process Equipment
- STV100K Surge Suppressors
- General Purpose Transformers
|
|
Mechanical |
| Indicators |
Indicating Lamps: 2 amber (overtemperature and bypass mode)
1 green (regulated output present) |
| Connections |
Field wired, terminal blocks |
| Size and Weight |
See Selection Table |
| Safety Agency Approvals |
UL1012 and UL1449-2
cUL (Canadian Standard C22.2 No 125) Complies with Part 15 Subpart J of FCC rules for a Class A computing device |
Environmental |
| Audible Noise |
Less than 50 dBA at 3 feet |
| Ambient Temperature |
0° to 40°C Operating, 0° to 80°C Storage |
| Operating Altitude |
10,000 feet without derating |
| Operating Humidity |
95% relative (non-condensing) |
Electrical |
| Power Ratings |
20, 30, 50, 75 KVA, Three Phase |
| Nominal Voltages |
See Selection Table |
| Input Voltage Range |
-25% to +15% of nominal rated voltage. |
| Output Voltage Range |
Regulated to ± 5% of nominal voltage with
an input voltage range of 25% to +15%. |
| Response Time |
Responds to any line variation in <1.5 cycles typical. |
| Technology |
Enhance Voltage Regulation (EVR), Microprocessor controlled electronic tap switching. 6 taps switched at zero current crossing with no output
interruption. |
| Operating Frequency |
57-63 Hz |
| Load Power Factor |
No Restriction |
| Insulation Resistance |
100 megohms from winding to core measured at 500 VDC |
| Efficiency |
96% typical |
| Overload Capability |
1000% of rated load for 1 second,
200% of rated load for 1 minute. |
| EMI |
Less than 0.2 gauss at a distance of 3 ft. |
Protection |
| Under Voltage |
Output voltage will switch to bypass mode when input is less than 50% of nominal. Regulated output voltage will be reestablished once input voltage is with specifications. |
| Short Circuit Protection |
Input circuit breaker |
| Over Temperature Protection |
Amber lamp indication of over temperature at approximately
180°C. Unit switches to by-pass mode until internal temperature is reduced to specified values. |
Noise Suppression Performance |
| Common Mode Noise Attenuation |
150 dB at 100 kHz |
| Normal Mode Noise Attenuation |
65 dB at 100 kHz |
| Surge Suppression |
Tested to ANSI/IEEE standard C62.41 A&B
(IEEE 587 Cat A and B), 1000-4, 1000-5 |
Output
KVA |
Catalog
Number |
VAC
Input |
Dimensions
H x W x D (in/cm) |
Ship
Weight
(lbs/kg) |
|
208
VAC Input, 208Y/120 VAC Output, 60 Hz |
| 20 |
63TAA320 |
208 |
42
x 28 x 26 (1016 x 712 x 661) |
600/273 |
| 30 |
63TAA330 |
208 |
42
x 28 x 26 (1016 x 712 x 661) |
750/341 |
| 50 |
63TAA350 |
208 |
42
x 28 x 26 (1016 x 712 x 661) |
950/432 |
| 75 |
63TAA375 |
208 |
42
x 28 x 26 (1016 x 712 x 661) |
1200/545 |
| 480
VAC Input, 208Y/120 VAC Output, 60 Hz |
| 20 |
63TCA320 |
480 |
42
x 28 x 26 (1016 x 712 x 661) |
600/273 |
| 30 |
63TCA330 |
480 |
42
x 28 x 26 (1016 x 712 x 661) |
750/341 |
| 50 |
63TCA350 |
480 |
42
x 28 x 26 (1016 x 712 x 661) |
950/432 |
| 75 |
63TCA375 |
480 |
42
x 28 x 26 (1016 x 712 x 661) |
1200/545 |
480
VAC Input, 480Y/277 VAC Output, 60 Hz |
| 20 |
63TCC320 |
480 |
42
x 28 x 26 (1016 x 712 x 661) |
600/273 |
| 30 |
63TCC330 |
480 |
42
x 28 x 26 (1016 x 712 x 661) |
750/341 |
| 50 |
63TCC350 |
480 |
42
x 28 x 26 (1016 x 712 x 661) |
950/432 |
| 75 |
63TCC375 |
480 |
42
x 28 x 26 (1016 x 712 x 661) |
1200/545 |
|
600
VAC Input, 208Y/120 VAC Output, 60 Hz |
| 20 |
63TDA320 |
600 |
42
x 28 x 26 (1016 x 712 x 661) |
600/273 |
| 30 |
63TDA330 |
600 |
42
x 28 x 26 (1016 x 712 x 661) |
750/341 |
| 50 |
63TDA350 |
600 |
42
x 28 x 26 (1016 x 712 x 661) |
950/432 |
| 75 |
63TDA375 |
600 |
42
x 28 x 26 (1016 x 712 x 661) |
1200/545 |
What's New |
Products |
Cross Reference |
Technical Support |
Contact Us |
Search |
Power Conditioner Home
© 2000
Sola/Hevi-Duty. All Rights Reserved.
Sola/Hevi-Duty Power Conditioner Products
|
 |