Catalog Number |
S4K4U6000 |
S4K6U10000 |
|
Model Rating |
4200W/6000VA at 120/240
(180° only - phase angle)
|
8000W/8660VA at 120/208 (120 or 240° only) |
4200W/5200VA at 127/220
(120 or 240° only - phase angle) * |
8000W/10000VA at 120/240 (180° only)* |
| 4200W/5200VA at 120/208 (120 or 240° only - phase angle) |
8000W/8660VA at 127/220 (120 or 240° only) |
| 4200W/6000VA at 115/230 (180° only - phase angle)* |
8000W/10000VA at 115/230 (180° only)* |
| 3780W/5400VA at 110/220 (180° only - phase angle)* |
7200W/9000VA at 110/220 (180° only)* |
| 3360W/4800VA at 100/200 (180° only - phase angle)* |
6400W/8000VA at 100/200 (180° only)* |
|
Dimensions - inches (mm) / Weight - lbs (kg) |
| Unit (W x D x H) |
6.9 x 24.2 x 16.9 (176 x 615 x 430)
|
10.5 x 29 x 16.93 (267 x 737 x 430) |
|
Shipping (W x D x H) |
13.2 x 27.8 x 20.9 (335 x 705 x 530) |
16.5 x 34.3 x 22.8 (420 x 870 x 580) |
|
Approx. Shipping Weight - lbs (kg) |
76.3 (34.6) |
118 (53.6) |
|
Input AC Parameters |
|
Nominal Operating Frequency |
50 or 60 Hz (Factory Default = 60) |
|
Factory Default VAC |
208 VAC at 120° phase angle (neutral required) |
|
L1-L2 Factory Default Input Phase Angle |
120° |
|
Allowable Input
Phase Angle
|
120, 180, 240°, Auto-sensing on application of AC
(Restrictions
for L-N voltages other than 120 VAC)
|
|
Factory Default |
L1-N, L2-N VAC 120 VAC nominal |
|
User Configurable L1-N, L2-N VAC |
100/110/115/120/127 VAC (May be modified using configuration
program) |
|
L1-N, L2-N, Operating Voltage
Range Without Battery Operation (Except 100 VAC L-N Operation) |
|
100% - 90% loading |
90 VAC - 140 VAC |
|
90% - 70% loading |
80 VAC - 140 VAC |
|
70% - 30% loading |
70 VAC - 140 VAC |
|
30% - 0% loading |
60 VAC - 140 VAC |
|
L1-N, L2-N, Operating Voltage
Range Without Battery Operation (100 VAC L-N Operation) |
|
100% - 70% loading |
80 VAC - 140 VAC |
|
70% - 30% loading |
70 VAC - 140 VAC |
|
30% - 0% loading |
60 VAC - 140 VAC |
|
L1-N, L2-N Max. Allowable VAC |
150 VAC |
|
Input Frequency w/o Battery Operation |
40 - 70 Hz |
|
Input Power Connection |
Hardwire Terminal Block 3W + G (L-L-N-G) |
|
Output AC Parameters |
|
Factory Default VAC |
120/208 VAC @ 120° phase angle |
|
L1-L2 Factory Default Output Phase Angle |
120° |
|
Allowable Output Phase Angle |
120, 180, 240° Auto-sensing on initial application of input AC |
|
Factory Default L1-N, L2-N VAC |
120 VAC nominal |
|
User Configurable L1-N, L2-N VAC |
100/110/115/120/127 VAC, ±3% |
|
Output Connections |
Hardwire Terminal Block 3W + G (L-L-N-G) |
|
Frequency |
50 Hz or 60 Hz, Nominal |
|
Waveform |
Sinewave |
|
Main Mode Overload |
200% for 8 cycles; 130% for 10 seconds with transfer to bypass |
|
Bypass Protection Limits |
|
Disable Bypass operation |
If input voltage exceeds ±15% of the nominal voltage |
|
Re-enable Bypass operation |
If input voltage returns to within ±10% of nominal output
voltage |
|
Disable Bypass operation |
When the input frequency prevents synchronous operation |
|
Environmental |
|
Operating Temp |
+32°F to +104°F (0°C to +40°C) |
|
Storage Temp |
+5°F to +122°F (-15°C to +50°C) |
|
Relative Humidity |
0% to 95%, non-condensing |
|
Operating Elevation |
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating |
|
Storage Elevation |
50,000 ft. (15,000 m) maximum |
|
Audible Noise |
<55 dBA, at 1 meter from the rear; <50 dBA, at 1 meter from the
front or sides |
|
Agency |
|
Safety |
UL 1778, c-UL Listed (Suitable for computer room applications) |
|
RFI/EMI |
FCC Part 15, Subpart B, Class A |
|
Surge Immunity |
IEEE/ANSI C62.41 Category A & B |
|
Transportation |
ISTA Procedure 1A |
|
Model Number |
S4K144BAT |
S4K288BAT |
|
Used w/ UPS Model |
S4K4U6000 |
S4K4U10000 |
|
Dimensions & Weights |
Unit (with bezel)
W x D x H - in (mm) |
3.5 x 24.2 x 17
(87 x 618 x 430) |
7.0 x 27 x 16.93
(178 x 686 x 430) |
|
Shipping W x D x H |
10.5 x 27.2 x 23
(268 x 692 x 585) |
13.0 x 34.3 x 22.8
(330 x 870 x 580) |
| Weight - lbs (kg) |
|
Unit |
93.6 (42.5)
|
41.6 (18.9) |
|
Shipping |
105 (47.6) |
50.6 (23) |
|
Battery Parameters |
|
Type |
Valve-regulated, non-spillable, flame retardant, lead acid |
|
Qty x V x Rating |
12 x 12V x 9.0 AH |
(2) x 12 x 12V x 9.0 AH |
|
Battery Mfg / Part # |
Yuasa / REW 45-12 FR |
|
Back-Up Time |
See Battery Run Time Charts |
|
Environmental |
|
Operating Temp |
+32°F to +104°F (0°C to +40°C) |
|
Storage Temp |
+5°F to +122°F (-15°C to +50°C) |
|
Relative Humidity |
0% to 95%, non-condensing |
|
Operating Elevation |
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating |
|
Storage Elevation |
50,000 ft. (15,000m) maximum |
|
Agency |
|
Safety |
UL 1778, c-UL Listed (Suitable for computer room applications) |
|
RFI/EMI |
FCC Part 15, Subpart B, Class A |
|
Transportation |
ISTA Procedure 1A |